Duplex Service Drop
APPLICATION of tano cable Duplex Service Drop cable
Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.
STANDARD of tano cable Duplex Service Drop cable
Tano Cable's duplex service drop cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire.
TanoCable's duplex service drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
CONSTRUCTION of tano cable Duplex Service Drop cable
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or crosslinked polyethylene (XLP). Neutral messengers are concentrically stranded 6201, AAC, or ACSR.
TECHNICAL DATA of tano cable Duplex Service Drop cable
Code
Phase Conductor
Bare
Weight
Allowable
Word
Neutral Messenger
Per 1000 ft. (lbs.)
Ampacities+
Size
Strand-
Insul.
Equiv.
Size
Strand-
Rated
XLP
POLY
XLP
POLY
(AWG)
ing
Thick.
Dia.
(kcmil)
ing
Strength
(mils)
(AWG)++
(lbs.)
6201 ALLOY NEUTRAL-MESSENGER
Chihuahua
6
1
45
6
30.58
7
1110
65
65
85
70
Vizsla
6
7
45
6
30.58
7
1110
68
68
85
70
Harrier
4
1
45
4
48.69
7
1760
99
99
115
90
Whippet
4
7
45
4
48.69
7
1760
103
103
115
90
Schnauzer
2
7
45
2
77.47
7
2800
157
157
150
120
Heeler
1/0
9
60
1/0
123.3
7
4460
250
250
205
160
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).
+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.
++ Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.
Code*
Phase Conductor
Bare
Weight
Allowable
Word
Neutral Messenger
Per 1000 ft. (lbs.)
Ampacities+
Size
Strand-
Insul.
Size
Strand-
Rated
XLP
POLY
XLP
POLY
(AWG)
ing
Thick.
(AWG)
ing
Strength
(mils)
(lbs.)
AAC NEUTRAL-MESSENGER
Pekingese
6
1
45
6
7
563
61
61
85
70
Collie
6
7
45
6
7
563
64
64
85
70
Dachshund
4
1
45
4
7
881
92
92
115
90
Spaniel
4
7
45
4
7
881
96
96
115
90
Doberman
2
7
45
2
7
1350
147
147
150
120
Malemute
1/0
9
60
1/0
7
1990
234
234
205
160
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).
+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.
Code*
Phase Conductor
Bare
Weight
Allowable
Word
Neutral Messenger
Per 1000 ft. (lbs.)
Ampacities+
Size
Strand-
Insul.
Size
Strand-
Rated
XLP
POLY
XLP
POLY
(AWG)
ing
Thick.
(AWG)
ing
Strength
(mils)
(lbs.)
ACSR NEUTRAL-MESSENGER
Setter
6
1
45
6
6/1
1190
72
72
85
70
Shepherd
6
7
45
6
6/1
1190
75
75
85
70
Eskimo
4
1
45
4
6/1
1860
110
110
115
90
Terrier
4
7
45
4
6/1
1860
115
115
115
90
Chow
2
7
45
2
6/1
2850
176
176
150
120
Bull
1/0
9
60
1/0
6/1
4380
280
280
205
160
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).
+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.
get more information: http://www.tanocable.com/
skype:tanocable
Tel.:+86-371-60306197 +86-18937105488
Less ...