500 KV
XLPE Insulated Power Cable
Standard
We produced according to National Standard of GB/T 22078.2-2008 of the People’s Republic of China.
Range of application
It is suitable for
single-core cable’s installation and operation under normal conditions of rated voltage 290/500 KV, but it is not suitable for cable in special use, such as
submarine cable.
Characteristics of
XLPE cable
●Rated voltage of cable is U0=290 KV、U=500 KV、Um=550 KV.
●The allowable maximum temperature of cable conductor is 90℃ when it runs in normal, and 250℃ when it short circuited (Longest time is 5 s).
●The allowable minimum bending radius is 20 times of cable outside diameter when installed. After installation , the minimum bending radius is recommended for 15 times of cable outside diameter.
Service environment( Place )
●
Lead sheath cable, is suitable for environment with more serious corrosion but no much nitric acid, acetic acid and organic matter ( Such as mud, coal and strong alkaline corrosion matter with technical force, stress and vibration etc.)
●
Aluminium sheath cable, is suitable for environment with minor corrosion and required to bear a certain mechanical force ( For example, connected with transformer directly and laying at bridge opening or in shaft etc.)
●Metal plastic compound sheath cable is suitable for general damp and warm place , no corrosion or light corrosion and no direct contact with water and bear not so much technical force , pulling force , stress and vibration.
●
PVC outer sheath cable is mainly used in cable line with general fire-proof requirement and insulation requirement for outer sheath.
●PE outer sheath cable is mainly suitable for directly buried laying cable line with higher requirement on outer sheath insulation, low temperature environment under 20℃, or soaked place by chemical liquid and low toxicity requirement when cable burns, when PE outer sheath is used in tunnel or shaft , fire-control and flame-retardant measures should be adopted if necessary.
Model and Name of product
Model
Name of cable
Copper core
YJLW02
XLPE insulated corrugated aluminium sheath or welding
aluminium sheath PVC sheath power cable
YJLW03
XLPE insulated corrugated aluminium sheath or welding aluminium sheath PE sheath power cable
YJLW02-Z
XLPE insulated corrugated aluminium sheath or welding aluminium sheath longitudinally water blocking PVC sheath power cable
YJLW03-Z
XLPE insulated corrugated aluminium sheath or welding aluminium sheath longitudinally water blocking PE sheath power cable
YJQ02
XLPE insulated lead sheath PVC sheath power cable
YJQ03
XLPE insulated lead sheath PVC sheath power cable
YJQ02-Z
XLPE insulated lead sheath PVC sheath longitudinally water blocking power cable
YJQ03-Z
XLPE lead insulated lead sheath PV sheath longitudinally water blocking power cable
Conductor structure , specifications , insulation thickness
Specifications Conductorcross-section (mm2)
structure
Minimum number of single wire in conductor
Maximum of conductordirect-current resistance(Ω/km)
Insulation nominal thickness
800
Round conductor/Segmental conductor
53
0.0221
34
1000
Segmental conductor
170
0.0176
33
1200
Segmental conductor
170
0.0151
33
1400
Segmental conductor
170
0.0129
32
1600
Segmental conductor
170
0.0113
32
1800
Segmental conductor
265
0.0101
31
2000
Segmental conductor
265
0.0090
31
2200
Segmental conductor
265
0.0083
31
2500
Segmental conductor
265
0.0073
31