Rated Voltage 0.6/1.0 KV and Below
PVC Insulated Power Cable
Product Standard
GB/T 12706-2008 standard equivalent to IEC502(2004).
Usage
This product is suitable for use in rated AC voltage(U0/U) 0.6 / 1.0 KV and below transmitting and distributing circuit .
Property for Use
a. Allowed maximum work temperature is 70 ℃ , for short circuit(5s), conductor maximum temperature is 160 ℃ .
b. While laying cable, the environmental temperature should not be less than 0 ℃ , for bend radius , should be not less than 10 times of cable overall diameter.
Note: Huiyou Cable supply PVC Insulated Power Cable, which include
HV power cable and
1.0kv Power Cable . Our products have high quality and competitive prices. By the way, Our factory can produce refractory 90 ℃ and 120 ℃
power cable
Type and Name
For cable type and name see table 1
Type
Product Name
VV VLV
PVC insulated, PVC sheathed power cable
VV22 VLV22
PVC insulated, steel belt armored, PVC sheathed power cable
Specifications
For cable specifications see table 2
Nominal cross-sectional area mm2
Master Core
Neutral Core
4
2.5
6
4
10
6
16
10
25
16
35
16
50
25
70
35
95
50
120
70
150
70
185
95
240
120
3+1 Core Cable Neutral Core Cross . Section see table 3
Model
Number of Cores
Nominal cross-sectional area mm2
VV
1
1.5~400
VLV
2.5~400
VV22
10~400
VLV22
10~400
VV
2
1.5~185
VLV
2.5~185
VV22
4~185
VLV22
4~185
VV
3
1.5~240
VLV
2.5~240
VV22
4~240
VLV22
4~240
VV
3+1
4~240
VLV
4~240
VV22
4~240
VLV22
4~240
VV
4
2.5~240
VLV
2.5~240
VV22
4~240
VLV22
4~240